Abus-technologies LPI-PT Loop Powered Indicator Instrukcja Użytkownika Strona 6

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 10
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 5
ABUS TECHNOLOGIES INC.
6
LPI-PT
4. ORDERING DETAILS
TYPE DESCRIPTION
Product
LPI-PT Loop Power Indicator for Pressure Transmitter
Transmitter
Output
D 4~20 mA DC
Alarm
N
No Alarm
1 1-Alarm
2 2-Alarm
Accessories
N None
Y Screw and Packing Gasket
Example: LPI-PT > D > N > N
5. CONNECTIONS
To connect the LPI-PT simply plug into an existing transmitter by means of a
special adaptor for the DIN43650 plug.
Supply voltage: Device takes power directly from measuring current. Please allow for
an additional loop voltage drop of 3 Volts.
Caution: Wrong electrical connection may lead to the destruction of the device.
Mind the maximum input current rating of 40 mA under any circumstances!
Electrical connections DIN 43650
2-wire
system
Supply + 1
Supply - 2
Ground Ground Contact
Przeglądanie stron 5
1 2 3 4 5 6 7 8 9 10

Komentarze do niniejszej Instrukcji

Brak uwag